PID Chap. 1 - The Process

The Feedback Control Loop


 

The system measures the process, compares it to a setpoint, and then manipulates the output in the direction which should move the process toward the setpoint.

 


Valve Linearity

 

Valves are usually non-linear. That is, the flow through the valve is not the same as the valve position. Several types of valves exist:

    Linear

    Same gain regardless of valve position

    Equal Percentage

    Low gain when valve is nearly closed

    High gain when valve is nearly open

    Quick Opening

    High gain when valve is nearly closed

    Low gain when valve is nearly open

     

     

As we will see later, the gain of the process, including the valve, is very important to the tuning of the loop.

• If the controller is tuned for one process gain, it may not work for other process gains.


Valve Linearity:
Installed characteristics

 

The flow vs. percent open curve changes due to the head loss in the piping

 

At low flow, the head loss through the pipes is less, leaving a larger differential pressure across the valve.

At high flow, the head loss through the pipe is more, leaving a smaller differential pressure across the valve.

 

The effect is to increase the non-linearity of most valves.


Fail Open Valves

Valves are usually either: Fail Closed, air to open or

Fail Open, air to close

• Regardless of the way the valve operates, the operator is interested in the knowing and adjusting the position of the valve, not the value of the signal. "Up is always open"

• All controllers have some means of indicating the controller output in terms of the valve position. When the operator increases the output as indicated on the controller, the valve opens.

Indication Inversion

>

The output indication is inverted.

The controller action takes the valve action into acount.

The flow loop is direct acting.

Most analog controllers work like this.

Signal Inversion

The output signal is inverted. The controller action ignores the valve action.

The flow loop is reverse acting. Some distributed control systems work like this.

back to index

go to chapter 2: the process response


ControlSim  The PID controller and process simulator based on MS Excel spread sheets.    $45.00 Click here to get more details, buy, and download

Buy and download my eBook: The PID Control Algorithm: How It Works, How To Tune It, and How to Use It. 2nd ed. 62pp
Adobe .pdf file                      only $15

visa-mclogo.gif (2156 bytes) Most major credit cards accepted.
Get more details, buy, and download

Apartments in Ballantyne in South Charlotte, NC.

Thousand Acre Swamp Hike Schedule
A schedule of the 2006 public hikes at Thousand Acre Swamp in Penfield, NY